| Pressure Temperature
Diagram |
 |
| . |
| Typical
Flow Rate Measuring Range for FloSite Sensors |
|
Pipe
Size
Sched. 80 PVC |
Fluid
Velocity (ft/sec) |
Flow
(gpm) |
| Min |
Max |
Min |
Max |
| 1/2" |
0.529 |
7.827 |
0.4 |
8.0 |
| 3/4" |
0.574 |
7.185 |
0.8 |
10.0 |
| 1" |
0.871 |
6.531 |
2.0 |
15.0 |
| 1-1/4" |
0.525 |
7.884 |
2.0 |
30.0 |
| 1-1/2" |
0.538 |
7.171 |
3.0 |
40.0 |
| 2" |
0.65 |
7.55 |
6.0 |
70.0 |
| 2-1/2" |
0.752 |
7.523 |
10.0 |
100.0 |
| 3" |
0.986 |
7.395 |
20.0 |
150.0 |
| 4" |
0.973 |
7.645 |
35.0 |
275.0 |
| 6" |
1.225 |
7.971 |
100.0 |
650.0 |
| 8" |
1.577 |
7.719 |
225.0 |
1100.0 |
| Based on water at 60F,
max 8 ft/sec velocity to minimize water hammer |
| . |
| Flow
Sensor Accuracy Comparison |
 |
Flo-Site Flow Sensors have an accuracy
of ± 1% of indicated flow over the full measuring range, unlike
other flow sensors with accuracy stated as a percentage of full scale (maximum
flow). |
|
| . |
 |
|